Worked example: a pressure transmitter
A pressure transmitter is configured for 0–16 bar gauge. A calibrated meter measures 12.00 mA. This corresponds to (12 − 4) / 16 = 0.5 of span. The expected measurement is 8.00 bar(g).
| Injected current | Percent of span | Expected indicated pressure | What to compare |
|---|---|---|---|
| 4.00 mA | 0% | 0.00 bar(g) | Raw AI counts, scaled tag, HMI value |
| 8.00 mA | 25% | 4.00 bar(g) | Linearity and engineering units |
| 12.00 mA | 50% | 8.00 bar(g) | Midspan agreement |
| 16.00 mA | 75% | 12.00 bar(g) | Upper-half linearity |
| 20.00 mA | 100% | 16.00 bar(g) | Top-of-range and alarms |
These are expected mathematical readings, not measured accuracy data or a certified calibration certificate.
A troubleshooting sequence that preserves evidence
- Record the tag and range. Confirm the tag, units, configured sensor span, AI channel mapping, PLC/DCS scaling, HMI units and historian scaling. A transmitter can be set to a different range from the control system.
- Establish a safe test state. Obtain the permit, isolate or simulate only through authorized procedures, and identify whether the signal drives alarms, trips, or permissives. Never inject signals into a live safety function without an approved test arrangement.
- Measure independently. Use a suitable loop meter or source, document instrument calibration status and verify polarity, supply, wiring and barriers according to the device manual.
- Compare stages. Record source current, field terminal current, AI diagnostic/current or raw counts, engineering-unit tag and HMI display. A discrepancy between adjacent stages narrows the cause.
- Challenge nominal points. Check at least low, mid and high points appropriate to the approved procedure. Record as-found data before making adjustments and as-left results afterward.
- Restore and prove normality. Remove forces and jumpers, reinstate alarms/interlocks, confirm normal operating state and retain signed test records where required.
Common mismatch patterns
| Observation | Possible causes to investigate | Evidence to capture |
|---|---|---|
| Correct meter current, wrong displayed value | AI channel assignment, incorrect LRV/URV, duplicate scaling, unit conversion, source mode | Meter reading + raw AI + tag + HMI snapshot |
| Constant zero/invalid input | Open circuit, power loss, fuse, polarity, failed transmitter, disabled channel | Loop voltage/current, channel diagnostic, configuration |
| Noisy/unstable value | Process fluctuation, grounding/shielding, EMC, sensor instability, filter settings | Time series at source and input, wiring/ground study |
| Unexpected high/low fault current | Device-specific configured diagnostics or out-of-range process | Device manual and diagnostic status; do not assume universal thresholds |
Important limits
Two-wire transmitters require enough compliance voltage for the transmitter, cabling, barriers and input burden. An apparent scaling problem can be an electrical loading problem. The current alone does not identify a unique failure, and nominal 4–20 mA scaling does not determine alarm thresholds or safety integrity.
Technical source and context
For consistent instrument tag identification and diagram conventions, see ISA-5.1 instrumentation symbols and identification. That standard concerns identification and symbols, not certification of the scaling example. Confirm analog current conventions and diagnostics using the specific device and controller documentation.
Related utilities: 4–20 mA converter · FAT/SAT evidence checklist.