A reproducible 400 V motor example
Consider a three-phase load with measured line-to-line RMS voltage of 400 V, line current of 25 A, power factor of 0.85 and estimated motor efficiency of 90%. First calculate apparent power: √3 × 400 × 25 ÷ 1000 = 17.321 kVA. Multiplying by 0.85 gives 14.722 kW electrical real input. At 90% assumed efficiency, the estimated useful shaft output is 13.250 kW. The reactive power magnitude is approximately 9.124 kvar under the sinusoidal assumption. None of those values is the motor's nameplate rating.
As a simple cross-check, electrical input power must not be lower than the modeled shaft output when efficiency is no greater than one. Apparent power must be at least as large in magnitude as real power. These are useful error checks, not evidence that a load is balanced or that a power measurement is accurate.
Four quantities that should not be confused
| Quantity | Meaning | Source or limitation |
|---|---|---|
| Real input power (kW) | Average active electric power supplied to the motor | Use a suitable true-power instrument when the waveform is distorted |
| Apparent power (kVA) | RMS voltage–current product adjusted for three phases | Useful for electrical loading; not the same as kW |
| Reactive power magnitude (kvar) | Quadrature component under sinusoidal conditions | This calculator cannot identify leading/lagging direction or harmonic effects |
| Shaft output (kW) | Mechanical power available to drive the load | Requires actual operating efficiency, torque/speed measurement, or a justified estimate |
When the simple equation is not appropriate
A variable-frequency drive (VFD) changes the picture. The motor terminals see a PWM waveform, and values from an ordinary handheld multimeter may not represent true power or power factor. For VFD systems, use the drive's validated metering or a power analyzer appropriate to the measurement point and waveform. Measure drive input and motor output separately if the question includes drive efficiency. Do not use the motor output estimate as a complete drive-and-motor-system efficiency result.
Unbalanced supply conditions require individual phase measurements and a suitable three-phase power analyzer. Significant harmonics require care with the relationship between displacement factor and true power factor. The familiar Q = √(S² − P²) relationship can include distortion effects if interpreted as physical fundamental reactive power, so the displayed kvar is explicitly a sinusoidal-model magnitude, not a verified power-quality measurement.
Commissioning and troubleshooting checklist
- Record all three line-to-line voltages and all three currents under steady, representative load; do not rely on a single phase reading when imbalance is suspected.
- Record the instrument, its measurement category, calibration status and whether it reports true real power, power factor and harmonics.
- Check the nameplate supply rating, frequency, connection, full-load current, efficiency class, speed and any manufacturer performance curves.
- When estimating shaft output, use efficiency at the actual load point. Full-load efficiency is not automatically applicable to part-load operation.
- Compare measured kW and operating hours before estimating energy consumption. A momentary kW reading does not describe an entire production shift.
- Investigate deviations against the load process, bearings, alignment, belt losses, driven equipment and VFD operating state. Do not conclude that high current alone proves overloading.
Formula provenance and further reading
The U.S. Department of Energy's Determining Electric Motor Load and Efficiency states the balanced three-phase input power relationship P = √3 × V × I × PF / 1000, identifying voltage and current as RMS quantities. Schneider Electric's Electrical Installation Guide: Definition of reactive power explains real, apparent and reactive power and their relationships for balanced sinusoidal loads. These are formula references, not endorsements of PROFENG or a certification of this page.
For related workflows, use the three-phase power calculator, the pump shaft power estimator and our FAT/SAT evidence checklist. For unresolved calculations, see the corrections process.