Airflow from ACH Calculator: worked example
This example is generated from PROFENG's own default input set and the implemented relationship. It is not copied from a cited publication.
Relationship
V̇ = ACH×room volume/3600
This calculator determines required airflow from target air changes, room volume. Use it for HVAC and building-services screening with transparent air, thermal or flow assumptions.
Inputs
- Target air changes (ach) = 6 ACH
- Room volume (volume) = 300 m³
Working
(6)*(300)/3600 = 0.5 m³/s
Required airflow: 0.5 m³/s
Assumptions and limits
- Air or fluid properties are represented by the entered values.
- The calculation represents steady operation unless the formula explicitly includes time.
- Room, duct or envelope geometry is idealized by the displayed relationship.
- ACH represents the target air-change rate for the effective room volume.
- The result is a steady average airflow and does not by itself establish ventilation-code compliance.